CVE-2019-18336

7.5 HIGH
Published: March 10, 2020 Modified: June 02, 2026
View on NVD

Description

A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V3.X.17), SIMATIC TDC CP51M1 (All versions < V1.1.8), SIMATIC TDC CPU555 (All versions < V1.1.1), SINUMERIK 840D sl (All versions < V4.8.6), SINUMERIK 840D sl (All versions < V4.94). Specially crafted packets sent to port 102/tcp (Profinet) could cause the affected device to go into defect mode. A restart is required in order to recover the system. Successful exploitation requires an attacker to have network access to port 102/tcp, with no authentication. No user interation is required. At the time of advisory publication no public exploitation of this security vulnerability was known.

AI Explanation

Get an AI-powered plain-language explanation of this vulnerability and remediation steps.

Login to generate AI explanation

CVSS v3.x Details

0.0 Low Medium High Critical 10.0
Vector String
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

References to Advisories, Solutions, and Tools

Patch Vendor Advisory Exploit Third Party Advisory
https://cert-portal.siemens.com/productcert/pdf/ssa-508982.pdf
Source: productcert@siemens.com
Vendor Advisory
https://cert-portal.siemens.com/productcert/pdf/ssa-508982.pdf
Source: af854a3a-2127-422b-91ae-364da2661108
Vendor Advisory

2 reference(s) from NVD

Quick Stats

CVSS v3 Score
7.5 / 10.0
EPSS (Exploit Probability)
1.7%
74th percentile
Exploitation Status
Not in CISA KEV

Weaknesses (CWE)

Affected Vendors

siemens